Description
ECL155-15E Bussmann Transformer Protection Indicating Cartridge Fuse 15A 15.5 kVAC Cylindrical, Blade Terminal (Bolt) Bolt Mount, E-rated medium voltage, current-limiting fuses for transformer and feeder protection.
Construction:
Filament wound, glass epoxy fuse tube, with silica filler, and silver-plated copper terminals and endcaps containing a silver element in a double concentric helical configuration.
Ratings:
Volts: 15.5kV
Amps: 10-300A
IR: 63kA Sym. (10-200A); 50kA Sym. (250-300A)
Agency Information:
Meets E requirements per ANSI C37.46, Meets General Purpose requirements per ANSI C37.40.
Features and Benefits
• Clip-lock double barrel fuse design assures positive installation
• The filament wound, glass epoxy fuse tube provides UV and moisture protection, making these medium voltage fuses suitable for both indoor and outdoor applications
• Open fuse indication (indicator travel distance is 16mm) easily integrates into automation schemes
• 50/60 Hz operating frequency make these fuses applicable world-wide
Typical Applications
• 15.0kV Transformer Primary Protection
• 15.0kV Feeder Circuit Protection
• 15.0kV Voltage Switches
• 15.0kV Metal-enclosed Switchgear
Current-limiting medium voltage fuses are classified into three categories:
Full Range – defined by ANSI as “a fuse capable of interrupting all currents from the maximum rated interrupting current down to the minimum continuous current that causes melting of the fusible element(s), when the fuse is applied at the maximum ambient temperature specified by the manufacturer.” It is able to interrupt any normal 60 cycle current that will melt its element.
General Purpose – defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting current down to the current that causes elting of the fusible element in one hour.” Not all currents fall within this range. It is possible to receive an overcurrent lower than the value given by the one hour criterion.
Back-up – defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting current down to the rated minimum interrupting current.” The minimum rated interrupting current is the lowest current that the fuse will be able to clear properly. This creates a need to place a low current interrupting device in series with the back-up rated fuse.
Mfr: Eaton – Bussmann Electrical Division
Mounting Type: Bolt Mount
Fuse Type: Cartridge
Current Rating (Amps): 15A
Voltage Rating AC: 15.5 kVAC
Breaking Capacity @ Rated Voltage: 63kA
Features: Indicating
Size / Dimension: 0.763″ L x 0.118″ W (19.38mm x 3.00mm)
Datasheet: Fuse ECL155
Catalog Number Cross Reference
| Bussmann | Ferraz-Shawmut New Catalog # |
Ferraz-Shawmut Old Catalog # |
| ECL155-10E | A155C1DORO-10E | 225-007-967 |
| ECL155-15E | A155C1DORO-15E | 225-007-968 |
| ECL155-20E | A155C1DORO-20E | 225-007-969 |
| ECL155-25E | A155C1DORO-25E | 225-007-970 |
| ECL155-30E | A155C1DORO-30E | 225-007-971 |
| ECL155-40E | A155C1DORO-40E | 225-007-972 |
| ECL155-50E | A155C1DORO-50E | 225-007-973 |
| ECL155-65E | A155C1DORO-65E | 225-007-974 |
| ECL155-80E | A155C1DORO-80E | 225-007-975 |
| ECL155-100E | A155C1DORO-100E | 225-007-976 |
| ECL155-125E | A155C2DORO-125E | 225-007-977 |
| ECL155-150E | A155C3DORO-150E | 225-007-978 |
| ECL155-200E | A155C3DORO-200E | 225-007-979 |
| ECL155-250E | A155C3DORO-250E | 225-007-980 |
| ECL155-300E | A155C3DORO-300E | 225-007-981 |